Product description:
The ZBF-12V-7A-17Ah cabinet buffer power supply is distinguished by an output voltage of 12 V and a current of 7 A, the rated power is 100 W.The kit includes the Delta PMT-12V100W1AA power supply . It is enclosed in a metal housing measuring 28.5 x 28 x 8 cm, adapted for wall mounting inside buildings (it is not airtight). One 17/18 Ah battery will fit inside.
Two LEDs indicating the power status (DC OK and AC OK) are led out on the cabinet door.
NOTE: The kit does not include a battery.
The most important features:
- rated power: 102 W
- output current (load + BAT): 7.39 A
- rated load current: 6.8 A
- charging current: 0.59 A
- space for a 17/18 Ah battery
- box dimensions: 28.5 x 28 x 8 cm
- universal input voltage range
- includes high quality PMT-12V100W1AA power module from DELTA ELECTRONICS
- output protections: overload, short circuit, overvoltage, thermal
- battery protection: incorrect connection before deep discharge
- housing protections: tamper
- charging current control
- free air cooling
- LED AC OK and DC OK optical signaling
| PMT-12V100W1AA | |
| Input Parameters | |
| Nominal input voltage | 100 - 120 V AC 200 - 240 V AC |
| Input voltage range | 90 - 132 V AC 180 - 264 V AC |
| Nominal frequency | 50 - 60 Hz |
| frequency range | 47 - 63 Hz |
| Input current | <2 A at 115 V AC <1.2 A at 230 V AC |
| Efficiency at 100% load | > 86% |
| Maximum starting current (cold start) | <36 A at 230 V AC |
| Leakage current | <1 mA at 240 V AC |
| Output Parameters | |
| Nominal output voltage | 12 V DC |
| Output voltage tolerance | 1% |
| Output voltage range | 11.4 - 13.2 V DC |
| Output current | 8.5 A. |
| Output power | 102 watts |
| Stabilization from network changes | <0.5% (100 - 132/200 - 264 V AC) |
| Stability from load changes | <0.5% (100 - 132/200 - 264 V AC) |
| PARD (20 MHz) | <150 mVpp |
| Fixing time | <20 ms at 100% load and nominal voltage |
| Rise time | <500 ms at 100% load and nominal voltage |
| Holding time | > 25 ms at 115 V AC (100% load) |
| Other features | |
| Permissible storage temperature | From -25 to 85 degrees Celsius |
| Permissible operating temperature | From -10 to 70 degrees C. |
| Permissible humidity | 10% -95% RH non-condensing |